Trung tâm báo cháy 16 kênh DETECTOMAT DCC8
- Clear display and easy operation with LED displays and operation keys.
- Connection possibility for 16 conventional zones for the use with the CT 3000 fire detection components with up to 20 detectors per zone.
- Extension option via 4 zone modules for up to 16 conventional zones for CT 3000 fire detection components.
- Integrated power supply according to EN 54-4:A2 2006.
- Independent connection of detector and signalling device zones.
- Integrated 'one-man-revision mode'.
- Manual control of signalling devices via seperate input.
- Programming options such as alarm delay.
- Panel network of max. two fire control panels.
Thông số ky thuật
Model |
DCC8 |
Supply Voltage |
230 VAC ( ±10 %) |
Emergency Supply |
1 x 12 V/ 18 Ah |
Quiescent Current |
2 to 10 mA |
Alarm Current |
10 mA to 110 mA |
Output |
4 x 24 V/300 mA monitored for signaling devices; 2 relay outputs 60 V DC/120 V AC/3A for alarm and fault |
Ambient Temperature |
-5°C to +40°C |
Humidity |
max. 95% |
Protection class |
IP30 |
Dimensions (H x W x D) |
345 x 455 x 128 mm |
Weight |
4,26 kg (w/o battery) |
Material |
ABS, Glass |
Standards |
EN 54-2: 1997/A1: 2006; EN 54-4: 1997/A2: 2006 |
Remarks |
Accessories: part-no. 32653, Type GE 4: 4 zone extension, part-no. 32654, Type SE 4: 4 signaling device lines extension, part-no. 32655, Type RM8: relay-module, 8 relay 1 A/12 V |
Display |
16 LEDs for status indication - (additionally 8 LEDs with etension); 6 keys for operation and programming |
Power Supply |
24 VDC/ 1A |